User`s guide

Quick Reference 1
Series N8700 User’s Guide 13
J2 Sense Connector
1 Remote sense (+)
2 Local sense (+)
3 Not used
4 Local sense ()
5 Remote sense (–)
The factory-shipped configuration is shown in the figure.
SW1 Setup Switch
The factory-shipped setting is Down for all switches.
1 Output voltage, voltage
programming
Down: The output voltage is programmed by the front panel.
Up
: The output voltage is programmed by the external voltage signal.
2 Output current, voltage
programming
Down: The output current is programmed by the front panel.
Up
: The output current is programmed by the external voltage signal.
3 Programming range
(voltage/resistance)
Down: The remote programming range is: 0 5V / 05KΩ.
Up
: The remote programming range is: 0 10V / 0 10KΩ.
4 Voltage and Current
monitoring range
Down: The remote monitoring range is: 0 5V.
Up
: The remote monitoring range is: 0 10V.
5 Shut-Off Logic Select Down: OUT OFF = Low (0 0.6V) or short; OUT ON = High (2V 15V) or open.
Up
: OUT OFF = High (2V 15V) or open; OUT ON = Low (0 0.6V) or short.
6 Not Used
7 Output voltage, resistive
programming
Down: The output voltage is programmed by the front panel.
Up
: The output voltage is programmed by the external resistor.
8 Output current, resistive
programming
Down: The output current is programmed by the front panel.
Up
: The output current is programmed by the external resistor.
9 – Enable/Disable control Down: The J1 Enable+/Enablepins are not active.
Up
: The J1 Enable+/Enablepins are active.
1
2
3
4
5
6
7
8
9