Specifications

79
Low-Profile Modular Power System
20-300 W GPIB (Continued)
Specific ation s
(at 0° to 55°C, and
derated above 40°C)
M
ore detailed specifications at
www.agilent.com/find/N6700
High Performance DC Power Supplies speed and accuracy for test optimization
N6731B N6732B N6733B N6734B N6735B N6736B
N6760 family
The Agilent N6760 family of precision
DC power modules provides precise
control and measurements in the
milliampere and microampere region
with the ability to simultaneously
digitize voltage and current, and
capture those measurements in an
oscilloscope-like data buffer. These
precision DC power modules offer
dual ranges on both programming
and measurement and are ideally
suited for semiconductor and
passive device testing.
N6750/60 low noise outputs
This switching power supply
outperforms most linear power
supplies on the market with low
normal and common mode noise.
1
With an output change from no load to full load, up tp a maximum load-lead drop of 1 V per lead.
2
Applies from minimum to maximum programming range. (see Supplemental Characteristics)
Output ratings
Voltage 5 V 8 V 20 V 35 V 60 V 100 V
Current 10 A 6.25 A 2.5 A 1.5 A 0.8 A 0.5 A
Power 50 W 50 W 50 W 50 W 50 W 50 W
Programming accuracy
2
(at 23°C ±5°C)
Voltage 0.1% + 0.1% + 0.1% + 0.1% + 0.1% + 0.1% +
19 mV 19 mV 20 mV 35 mV 60 mV 100 mV
Current 0.15% + 0.15% + 0.15% + 0.15% + 0.15% + 0.15% +
20 mA 20 mA 20 mA 20 mA 20 mA 10 mA
Readback accuracy (at 23°C ±5°C)
Voltage 0.1% + 0.1% + 0.1% + 0.1% + 0.1% + 0.1% +
20 mV 20 mV 20 mV 35 mV 60 mV 100 mV
Current 0.15% + 0.15% + 0.15% + 0.15% + 0.15% + 0.15% +
20 mA 10 mA 5 mA 4 mA 4 mA 2 mA
Output ripple and noise (PARD)
(from 20 Hz 20 MHz)
CV peak-to-peak 10 mV 12 mV 14 mV 15 mV 25 mV 30 mV
CV rms 2 mV 2 mV 3 mV 5 mV 9 mV 18 mV
Load regulation
1
Voltage 5 mV 6 mV 9 mV 11 mV 13 mV 20 mV
Current 2 mA 2 mA 2 mA 2 mA 2 mA 2 mA
Line regulation
Voltage 1 mV 2 mV 2 mV 4 mV 6 mV 10 mV
Current 1 mA 1 mA 1 mA 1 mA 1 mA 1 mA
Transient response time (time to recover to within the settling band following a load
change from 50% to 100% and from 100% to 50% of full load.)
Voltage settling band ± 80 mV ± 80 mV ± 200 mV ± 200 mV ± 400 mV ± 500 mV
Time 200 µs 200 µs 200 µs 200 µs 200 µs 200 µs
Triggering
The N6700 MPS mainframe has
hardware trigger in/trigger out sig-
nals which permit the N6700 to be
synchronized with external events.
Output disconnect relays
Modules in the N6700 can be
individually ordered with optional
Output Disconnect Relays (option
761) or Output Disconnect/Polarity
Reversal Relays (option 760). With
option 761, Output Disconnect Relays,
mechanical relays disconnect both
the plus and minus side of the
power supply, including the sense
leads. With option 760, Output
Disconnect/Polarity Reversal
Relays switch the leads on both the
plus and minus side of the power
supply, including the sense leads,
resulting in a voltage polarity
reversal at the DUT.
Universal AC input
The N6700 has a universal input
that operates from 100-240 VAC,
50/60/400 Hz. There are no switches
to set or fuses to change when
switching from one voltage standard
to another. The AC input employs
power factor correction.
Choosing the Right DC Power
Modules to Meet Your ATE Needs
N6750 family
The Agilent N6750 family of high-
performance, autoranging DC power
modules provides low noise, high
accuracy and includes, auto-ranging
output capabilities enabling one
power supply to do the job of sev-
eral traditional power supplies. In
addition, it includes optional high-
speed test extensions that offers an
oscilloscope-like digitizer and ultra-
fast programming speed.