Product specifications

CI865 and TP865 – Satt I/O Interface Appendix A Hardware Units
330 3BSE036351-510 A
Indicators
Table 96. Satt I/O CI865 – Fault Finding
Designation/Color Function
Neither R(un) nor F(ault)
LED’s are ON
The CI865 unit is in the process of being
configured. Allow time for this to finalize.
If the condition persists, and no other unit LED on
the CEX-Bus is lit:
Check the CEX-Bus fuse inside the PM8xx
processor unit
Initiate a reset signal (INIT) from the PM8xx
processor unit
Replace the CI865 unit
F(ault) LED is ON The CI865 unit is in the process of being
restarted. Allow time for this to finalize.
Replace unit if the condition persists.
COM A/COM B LED is OFF Power OFF or Reset Mode
COM A/COM B LED is solid
green
Channel OK
COM A/COM B LED is
flashing green
Temporary error or need initial setup
COM A/COM B LED is solid
red
Module is broken, has to be replaced
COM A/COM B LED is
flashing red
Bad channel cable
COM A/COM B LED is railroad
red
The road is not configured right for the network
COM A/COM B LED is
flashing red/green
Network has data flow problem
COM A/COM B LED is railroad
red/green
Self test