Product specifications

CI865 and TP865 – Satt I/O Interface Appendix A Hardware Units
328 3BSE036351-510 A
CI865 and TP865 – Satt I/O Interface
Key Features
Provides one ControlNet port, (a BNC connector
located on the TP865 Baseplate).
Simple DIN-rail mounting.
Handles I/O scanning of up to 31 distributed I/O
nodes.
Pre-set, two-letter Alpha code locking device
installed in unit base prevents mounting of
incompatible components.
Supports Hot swap.
Description
The CI865/TP865 connects ControlNet to AC 800M. The
module makes it possible to use older Satt I/O system
(Rack I/O and Series 200 I/O) with the AC 800M
controller platform but it can not be used as a general
ControlNet interface. The TP865 Baseplate has one BNC
connector for connecting I/O racks. The baseplate has a
code lock, see Table 4 on page 75, that prevents
installation of an incorrect type of unit onto the TP865
Baseplate.
The CI865 expansion unit contains the CEX-Bus logic, ControlNet bus logic, CPU
and a DC/DC converter that supplies appropriate voltages from the +24 V supply,
via the CEX-Bus.