Product specifications

Section 5 Maintenance MOD5 Interface - CI872
3BSE036351-510 A 233
F(ault) LED is ON Possible Cause 1: The CI872 module is in the process of
upgrading the firmware (if the upgrade is in progress).
Corrective Action 1: Wait for the firmware to be upgraded.
Possible Cause 2: Fault in the CI872 module.
Corrective Action 2: Hot remove and hot insert the CI872
module.
Corrective Action 3: If the indication persists after
performing the corrective actions 1 and 2, then replace the
CI872 module.
R(un) LED is ON The green R(un) LED indicates that CI872 is operational.
Rx/Tx1, Rx/Tx2, and
Rx/Tx3 LEDs are flashing
There is one LED corresponding to each port on the CI872
module. When the LED corresponding to a port flashes, it
indicates that communication is happening on that particular
port.
Rx/Tx1, Rx/Tx2, Rx/Tx3
LED is OFF
Possible Cause 1: The fiber optic cable is not connected or
it is not connected properly to the port.
Corrective action 1: Do any of the following:
Check the corresponding optical cable connections,
that is, the connections for reversed transmitter and
receiver optical cables for that particular port, and the
connections on the DOW MOD5 controller.
Check the Network Controller Board (NCB) on the
MOD5 Controller connected to that particular port.
Possible Cause 2: The configuration is not downloaded
from the Hardware Tree (in the Control Builder) to the
controller.
Corrective Action 2: Ensure that the module is configured
in the Hardware Tree for the correct position and the
configuration is downloaded to controller.
Table 46. MOD5 Communication Interface, Type CI872 - Indications and Fault Finding (Continued)
Indication Possible Causes, and Corrective Actions (for faults)