Product specifications

FOUNDATION Fieldbus H1 – CI852 Section 5 Maintenance
212 3BSE036351-510 A
The network
problem is
proving very
difficult to solve
(continued).
Use an oscilloscope to check the communication signals for
abnormalities.
The oscilloscope must be of differential or battery
operated type.
Probes must have a minimum of 1 MOhm input
resistance, and less than 1000 pF input capacitance.
Disconnect sections of the network, including the Ethernet port
via the PM8xx processor unit, until it is reduced to a size that
functions correctly.
A hand-held fieldbus master unit should be used to make
connections at different points in the network.
Locate the unserviceable section by reconnecting the
sections one at a time. In the worst possible case, it may
be necessary to remove devices one by one to identify the
faulty item.
Cables can be checked using the ohmmeter (resistance)
function of a digital voltmeter. Isolate the power supply
and disconnect all other devices before making the check.
For large networks, a network analyzer should be
employed. The analyzer must be suitable for use on
FOUNDATION Fieldbus networks.
Table 32. FOUNDATION Fieldbus H1 CI852 – Fault-Finding (Continued)
Fault Possible Cause and Corrective Action