Product specifications
Section 2 Installation Installing the RS-232C Interface, CI853/TP853
3BSE036351-510 A 115
Installing the RS-232C Interface, CI853/TP853
CI853 is powered from the processor unit via the CEX bus and requires therefore no
additional external power source.
Use the following procedure to install the CI853/TP853:
1. Mount the unit onto the DIN-rail, see Mounting AC 800M Units onto DIN-Rail
on page 65 and Installing the PM86x/TP830 Processor Unit in Single
Configuration on page 78.
2. Connect the cable (maximum 15 m (16.4 yd)) to one of the contacts on the
baseplate. Connect the cable screen to the ground terminal within the connector
to ground the screen via CI583.
3. If cables longer than 15 m (16.4 yd.) are required, then a short distance modem
TC562 must be used. In this case mount the modem onto a DIN-rail in a
suitable position, connect a 24
V DC power supply to the modem and connect
cable TK853 from CI853 to the TC562 modem input terminals
4. Connect the TC562 modem output terminals to the outgoing cable.
The TC562 modem can be used for the following distances/speeds:
• Up to 1000 m (1100 yd) with transmission speed 19200 bit/s
• Up to 12000 m (13100 yd) with transmission speed 1200 bit/s
Connectors
Connect the RS-232C channels to the RJ45 connectors marked COM1 and COM2
on the TP853 Baseplate.
Table 14. CI853 RS23-C Interface – COM1 and COM2 Connectors
Pin Designation Direction Description
1–9 – – See COM3 on TP830, Ta ble 6 on page 85.
Note that there is no unit redundancy for the CI853 unit.