User`s manual

Setting Switch/
Jumper
Agilent E1482B VXI-MXI
Extender Module
Slot 0
(factory settings)
Agilent E1482B VXI-MXI
Extender Module
Non Slot 0
Trigger Input
Termination
S5
Trigger 50 terminated
Ext Clk SMB S6 Output external clock
MXIbus Terminating
Resistor Networks
--- Remove unless last device
in daisy chain
Installed
MXI Controller
Timeout Level
W8 MXIbus timeout disabled
MXIbus timeout =100 µs
VME BTO Level W6
VMEbus timeout = 100 µs VMEbus timeout = 200 µs
INTX Terminating
Resistor Networks
--- Remove unless last device
in daisy chain
Installed
MXIbus Fairness S2 Fairness enabled
Interlocked Arbitration S3 Interlocked
MXI System Controller S4 Not MXIbus controller MXIbus controller
Logical Address --- Set the logical address to
1, 2, or 3
Set the logical address to
the number above a
window boundary (e.g.
boundary = 128, logical
address = 129)
VXIbus Slot 0 Device S1, S8 Slot 0 Non-Slot 0
Front Panel
Pushbutton
S7 SYSRESET* asserted
VME BTO Chain
Position
W7 1 extender, slot 0 1 extender, non-slot 0
VMEbus Request Level W1 - W5 Level 3 requester
CLK10 Source W9, W10 On-board 10 MHz VXI-MXI
installed in slot 0
Do not source CLK10
CLK10 Mapping W1 - W3 CLK10 mapping disabled
Table 2-1. E1482B Slot 0 and Non Slot 0 Configurations
C-Size Configuration Guide Setting Up a Series 700 Computer 2-21