User's Manual
Installation 2 
Series N5700 User’s Guide  19 
Connecting the Line Cord 
WARNING 
SHOCK HAZARD The power cord provides a chassis ground through a third 
conductor. Be certain that your power outlet is of the three-conductor type 
with the correct pin connected to earth ground. 
FIRE HAZARD Use only the power cord that was supplied with your 
instrument. Using other types of power cords may cause overheating of the 
power cord, resulting in fire. 
NOTE 
The detachable power cord may be used as an emergency disconnecting 
device. Removing the power cord will disconnect ac input power to the unit. 
The AC input on the back of your unit is a universal AC input. It 
accepts line voltages in the range of 85 VAC to 265 VAC. The 
frequency range is 47 Hz to 63 Hz. 
The input current requirement of 750W units is 10.5A @ 100 VAC 
nominal and 5A @ 200 VAC nominal. The current requirement of 
1500W units is 21A @ 100 VAC nominal and 11A @ 200 VAC nominal. 
Input Connections for 750W units 
Connect the power cord to the IEC 320 connector on the rear of the 
unit. The IEC connector provides the safety ground connection when 
the AC cord is plugged into a grounded AC receptacle. 
If the wrong power cord was shipped with your unit, contact your 
nearest Agilent Sales and Service Office. 
Input Connections for 1500W units 
CAUTION 
Connection of this power supply to an AC power source should be made by a 
qualified electrician or other qualified personnel. 
The AC input connector is a 3-terminal wire clamp located on the 
rear panel. Use suitable wires and tightening torque as follows: 
•  Wire diameter: 12 AWG or 10 AWG 
•  Tightening torque: 6.5 - 7.0 in-lb 
Connect the cable to the AC input connector as follows: 
•  Strip the outside insulation of the AC cable approximately 10 
cm (4 in). Trim the wires so that the ground wire is 10 mm 
(0.4 in) longer than the other wires. Strip 14 mm (0.55 in) at 
the end of each of the wires. 