Specifications

42
Single-Output Autoranging 5, 10, 15 KW GPIB, LAN (LXI core), USB
(Continued)
More detailed specifications at
www.agilent.com/find/N8900
Basic DC Power Supplies essential features for a tight budget
Notes:
1
For purposes of Output Response Time, full load occurs at the full range output voltage and the maximum
output current available at the full output voltage
Specifications
(at to 55°C unless
otherwise specified)
N8931A N8932A N8934A N8935A N8937A
N8951A N8952A N8954A N8955A N8957A
Supplemental Characteristics (Non-warranted characteristics determined by design
that are useful in applying the product)
Output response time (total voltage excursion)
10% to 90%, of full load
1
≤ 30 ms ≤ 30 ms ≤ 30 ms ≤ 30 ms ≤ 30 ms
90% to 10%, of full load
1
≤ 80 ms ≤ 80 ms ≤ 80 ms ≤ 80 ms ≤ 80 ms
90% to 10%, at no load ≤ 30 s ≤ 10 s ≤ 10 s ≤ 10 s ≤ 10 s
Command response time < 25 ms < 25 ms < 25 ms < 25 ms < 25 ms
Current ripple & noise
CC rms 240 mA 66 mA 48 mA 48 mA 26 mA
Remote sense compensation
Volts/load lead 2 V 5 V 10 V 18 V 30 V
Over-voltage protection range 88 V 220 V 550 V 825 V 1650 V
Source effect
10% of AC input rating)
Voltage 16 mV 40 mV 100 mV 150 mV 300 mV
Current 255 mA 105 mA 45 mA 30 mA 15 mA
Output terminal isolation 300 V 300 V 300 V 300 V 300 V
208 VAC input
Voltage
187 to 240 VAC 187 to 240 VAC 187 to 240 VAC 187 to 240 VAC 187 to 240 VAC
Current 3 x 56 A 3 x 56 A 3 x 56 A 3 x 56 A 3 x 56 A
400 VAC input
Voltage
340 to 460 VAC 340 to 460 VAC 340 to 460 VAC 340 to 460 VAC 340 to 460 VAC
Current 3 x 28 A 3 x 28 A 3 x 28 A 3 x 28 A 3 x 28 A
208 & 400 VAC input
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Number phases 3 phase 3 phase 3 phase 3 phase 3 phase
Power factor >0.99 >0.99 >0.99 >0.99 >0.99