Specifications

Family of affordable, autoranging
system DC power supplies
The Agilent Technologies N8900
Series provides 5, 10, and 15 kW
autoranging, single-output program-
mable DC power for ATE applications
that require just the right amount of
performance at just the right price.
The N8900 Series power supplies’
autoranging output characteristic
enables unprecedented flexibility by
offering a wide range of voltage and
current combinations at full power.
Power supplies with “rectangular,”
or traditional, output characteris-
tics provide full power at only one
voltage and current combination.
Just one N8900 does the job of
multiple power supplies. It’s like
having many power supplies in one!
The N8900 Series provides stable
output power, built-in voltage
and current measurements, and
autoranging output voltage and
current from 80 to 1500 V and 10
to 510 A. These supplies offer many
system-ready features like multiple
standard I/O interfaces to simplify
and accelerate test-system develop-
ment and compact 3U design to
save rack space.
Basic DC Power Supplies essential features for a tight budget
Single-Output, Autoranging
5, 10, 15 KW GPIB, LAN (LXI core), USB
N8920A-N8924A, N8925A-N8930A
N8931A-N8937A, N8940A-N8944A
N8945A-N8950A, N8951A-N8957A
Notes: All specifications apply to >2% of voltage and >1% of current
1
20 MHz
2
20 Hz to 300 kHz
3
Time for output voltage to recover within 1% of its rated output for a load change from 10% to 90% of its
rated output current)
Specifications
(at to 55°C unless
otherwise specified)
N8920A N8921A N8923A N8924A
N8940A N8941A N8943A N8944A
Number of outputs 1 1 1 1
GPIB, LAN, USB Yes Yes Yes Yes
DC ratings
Voltage 0 to 80 V 0 to 200 V 0 to 500 V 0 to 750 V
Current 0 to 170 A 0 to 70 A 0 to 30 A 0 to 20 A
Power 5000 W 5000 W 5000 W 5000 W
Output ripple and noise
CV peak to peak
1
200 mV 300 mV 350 mV 800 mV
CV rms
2
16 mV 40 mV 70 mV 200 mV
Load effect (change from 0% to 100% of full load)
Voltage 40 mV 100 mV 250 mV 375 mV
Current 255 mA 105 mA 45 mA 30 mA
Programming accuracy
Voltage ≤ 80 mV ≤ 200 mV ≤ 500 mV ≤ 750 mV
Current ≤ 340 mA ≤ 140 mA ≤ 60 mA ≤ 40 mA
Measurement accuracy
Voltage ≤ 80 mV ≤ 200 mV ≤ 500 mV ≤ 750 mV
Current ≤ 340 mA ≤ 140 mA ≤ 60 mA ≤ 40 mA
Load transient response
Recovery time
3
≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms
V
1
I
1
I
2
I
3
Volts
P
1
P
2
P
3
Amps
V
2
V
3
Autoranging output - does the job of multiple power supplies
Up to 1500 V and up to 510 A
Built-in measurements and advanced programmable features
Protection from over-voltage, over-current, and over-temperature
Parallel units to create “one” power supply with greater than
100 kW of power
Small high density 3U package