Specifications
185
Choosing AC Line Voltage and Cord Options for your Agilent Power Products
DC Power Supplies, DC Electronic Loads, and AC Sources (Continued)
For more detailed specifications see the product manual at
www.agilent.com/find/power
These are the ONLY
connections used
when powering the
668XA and 669XA
Earth Gnd
V
(line-to-neutral)
Neutral
(never used)
V
(line-to-line)
V
(line-to-line)
OC
OB
OA
Delta
Wye
Cord 844 845 846 847 848
Options
Product/Family
NEMA IEC 309 NEMA CEE 7/7 BS 546
L6-30P 16-A L5-30P 16-A 15-A
#10AWG 1.5 mm
2
#10AWG 1.5 mm
2
1.5 mm
2
N/S America Denmark N. America Europe India
Japan Switzerland Korea South Africa
Austria, China
6030A, 31A, 32A, 35A N/A 8120-5570 8120-5565 8120-5567 8120-5569
6571A - 75A 8120-5546 N/A N/A N/A N/A
6671A - 75A 8120-5546 N/A N/A N/A N/A
6812B N/A 8120-5570 8120-5565 8120-5567 8120-5569
6813B 8120-6507 N/A N/A N/A N/A
66000A N/A 8120-5570 8120-5565 8120-5567 8120-5569
E4356A 8120-5546 N/A N/A N/A N/A
X
Y
G
8120-5565
W
L
G
E
N
L
E
L
N
E
L
N
Option 848
In a wye system
V
(line-to-neutral)
= V
(line-to-line)
√3
Note:
The countries or regions indicated
here are for general guidance only.
Local electrical codes governing
wire size, wire type (AWG or met-
ric) and plug type should be con-
sulted to determine which of these
available line cords/plugs is correct
in your country to make proper
connection to your AC mains.
Please consult a qualified, licensed
electrician for more information.
Products with 3-phase inputs
Some of the higher power products
exceed the capability of a single
phase line. Agilent offers several
power products which require
3-phase inputs, including the
5kW668XAand6.6kW669XA
DC source family. For 3-phase
power distribution up to the
building, there are two different
distribution systems in wide use:
delta, predominantly used in the
US; and wye predominantly used
in Europe. However, for service
inside the building, the 5 wire wye
is the predominant configuration.
Products which are delta loads,
are compatible with either delta
or wye. Agilent 3-phase products
are delta loads.
In selecting the correct operating
voltage for 3-phase products you
need to distinguish between the
line-to-line and the line-to-neutral
voltages. The line-to-line voltage
is the square root of 3 x the line-
to-neutral voltage. It is the line-to-
line voltage that is used to specify
the input voltage to be applied to
Agilent power products.