Specifications
110
Low-Profile Modular Power System
20-300 W GPIB (Continued)
Specifications
(at 0° to 55°C, and
derated above 40°C)
M
ore detailed specifications at
www.agilent.com/find/N6700
High Performance DC Power Supplies speed and accuracy for test optimization
N6731B N6732B N6733B N6734B N6735B N6736B
1
With an output change from no load to full load, up to a maximum load-lead drop of 1 V per lead.
2
Applies from minimum to maximum programming range. (see Supplemental Characteristics)
Output ratings
Voltage 5 V 8 V 20 V 35 V 60 V 100 V
Current 10 A 6.25 A 2.5 A 1.5 A 0.8 A 0.5 A
Power 50 W 50 W 50 W 50 W 50 W 50 W
Programming accuracy
2
(at 23°C ±5°C)
Voltage 0.1% + 0.1% + 0.1% + 0.1% + 0.1% + 0.1% +
19 mV 19 mV 20 mV 35 mV 60 mV 100 mV
Current 0.15% + 0.15% + 0.15% + 0.15% + 0.15% + 0.15% +
20 mA 20 mA 20 mA 20 mA 20 mA 10 mA
Readback accuracy (at 23°C ±5°C)
Voltage 0.1% + 0.1% + 0.1% + 0.1% + 0.1% + 0.1% +
20 mV 20 mV 20 mV 35 mV 60 mV 100 mV
Current 0.15% + 0.15% + 0.15% + 0.15% + 0.15% + 0.15% +
20 mA 10 mA 5 mA 4 mA 4 mA 2 mA
Output ripple and noise (PARD)
(from 20 Hz – 20 MHz)
CV peak-to-peak 10 mV 12 mV 14 mV 15 mV 25 mV 30 mV
CV rms 2 mV 2 mV 3 mV 5 mV 9 mV 18 mV
Load regulation
1
Voltage 5 mV 6 mV 9 mV 11 mV 13 mV 20 mV
Current 2 mA 2 mA 2 mA 2 mA 2 mA 2 mA
Line regulation
Voltage 1 mV 2 mV 2 mV 4 mV 6 mV 10 mV
Current 1 mA 1 mA 1 mA 1 mA 1 mA 1 mA
Transient response time (time to recover to within the settling band following a load
change from 50% to 100% and from 100% to 50% of full load.)
Voltage settling band ± 80 mV ± 80 mV ± 200 mV ± 200 mV ± 400 mV ± 500 mV
Time 200 s 200 s 200 s 200 s 200 s 200 s
Digitizer:
•Measurementpoints=1to512K
•Samplerate=0.000025Hzupto
200 kHz
I/O interface:
GPIB,LAN,USBstandard
Software driver:
•IVI-COM
•VXIPlug&Play
AC input:
•Inputratings:100–240VAC;
50/60/400 Hz
•Powerconsumption:
°
N6700B–1440VAtypical
(with power factor correction)
°
N6701A–1440 VA typical
(with power factor correction)
°
N6702A–1440 VA typical
@ < 180 VAC input
(with power factor correction)
°
N6702A–2200 VA typical
@ > 180 VAC input
(with power factor correction)
Regulatory compliance: European EMC
directive 89/336/EEC for Class A
products, Australian C-Tick mark,
This ISM device complies with
Canadian ICES-001. Cet appareil ISM
estconformeàlanormeNMB-001du
Canada. European Low Voltage
Directive 73/23/EEC.
Size:
•Height44.45mm;1.75in
•Width432.5mm;17.03in
•Depth(includinghandles)
585.6mm;23.06in(N6700B/N6701A)