User`s guide

3 - Installation
30
Figure 3-2. Remote Sense Connections
Remote Sense Leads
Testing has verified stable performance with the sense leads connected up to 20 inches from the phone.
However, for optimum performance, connect the sense leads as close as possible to the phone under test.
To minimize inductance, connect the sense leads as a separate twisted pair.
The sense leads are part of the dc source's feedback path and must be kept at a low resistance (less than
several ohms) to maintain optimal performance. Connect the sense leads carefully so that they do not
become open-circuited. If the sense leads are left unconnected or become open during operation, the dc
source will not regulate the output voltage. See "Open Sense Lead Protection".
Connect the remote sense leads only to the remote sense connections at the output connector and at the
location on the test fixture where you want to sense the output voltage. There must be not be any
continuity from the sense leads to earth ground or from the sense leads to the output leads other than at
the test fixture. The open sense detect circuit will check for continuity in the sense leads when the output
is turned.
Figure 3-3 shows how to connect remote sense leads and load leads when external disconnect relays are
included in the load path.
NOTE: In this arrangement, the output of the unit should be programmed OFF before the relays
are switched. This is because if the load leads are opened before the sense leads, the
overvoltage protection circuit will trip if it is enabled.
Local
Remote
SENSE
LOAD
TWIST PAIR
SENSE
SWITCH OUT
HP 66311A OUTPUT
CONNECTOR
+
_
-S - + +S
WIRE RESISTANCE
TWIST LEADS