Technical data

97
Choosing ac Line Voltage and Cord Options for your
Agilent Power Products
(Continued)
Power Products Catalog 2002-2003
For more detailed specifications see the product manual at
www.agilent.com/find/power
Agilent Technologies
Table 3A - 800 Series Line Cord Options (Available for high power products)
Power supply Option 601XA 657XA 6813B
series Number 603XA(1kW) 667XA
66000A, 6812B E4356A
Unterminated: 831 8120-5573 8120-5488 8120-5573
line cords 832 n.a. 8120-5490 8120-6502
without plugs 833 8120-5568 n.a. n.a.
834 8120-5566 8120-5545 8120-5566
Terminated: 841 8120-5572 8120-5491 8120-5572
line cords 842 n.a. 8120-5489 8120-6506
with plugs 844 n.a. 8120-5546 8120-6507
845 8120-5570 n.a. n.a.
846 8120-5565 n.a. n.a.
847 8120-5567 n.a. n.a.
848 8120-5569 n.a. n.a.
NOTE: If no line cord option is specified on the purchase order, an unterminated line cord will be shipped.
Table 3B - Unterminated Line Cords (Line cords without plugs)
Option Description
Number
Option 831 12 AWG, 3 wire; UL-Listed, CSA-certified, 8 ft, unterminated. Use for connection to
200-240 Vac mains. Note for 657XA or 667XA series, E4356A and 6813B: not acceptable
for use in Canada or Japan. Choose either -834 or -844 10 AWG power cord option.
Option 832 4-mm
2
wire size, 3 wire, 2.5 m; harmonized cordage; unterminated. Suggested for use in
Europe and other areas not listed.
Option 833 1.5-mm
2
wire size, 3 wire, 2.5 m; harmonized cordage; unterminated. Suggested for use in
Europe and other areas not listed. Note for 603XA and 66000 series: intended for connection
to 200-240 Vac service.
Option 834 10 AWG, 3 wire; UL-listed, CSA-certified; 8 ft, unterminated. Note for 601XA or 603XA series,
66000A or 6812B: required for connection to 100-120 Vac mains. For 657XA or 667XA series,
E4356A and 6813B: required for connection to 200-230 Vac mains in Canada or Japan.
Products with 3-Phase Inputs
Some of the higher power products
exceed the capability of a single
phase line. Agilent offers several
power products which require
3-phase inputs, including the
5kW 668XA and 6.6 kW 669XA
dc source family. For 3-phase
power distribution up to the
building, there are two different
distribution systems in wide use:
delta, predominantly used in the
US; and wye predominantly used
in Europe. However, for service
inside the building, the 5 wire wye
is the predominant configuration.
Products which are delta loads,
are compatible with either delta
or wye.
As shown in table 4, the delta has
only three current carrying con-
ductors; there is no neutral. The
wye configuration has four current
carrying conductors. In general,
the neutral should carry no signifi-
cant current. None of the Agilent
power products use the neutral
connection found on wye systems.
Do not connect the neutral to
ground.
In selecting the correct operating
voltage for 3-phase products you
need to distinguish between the
line-to-line and the line-to-neutral
voltages. The line-to-line voltage is
the square root of 3 x the line-to-
neutral voltage. It is the line-to-line
voltage that is used to specify the
input voltage to be applied to
Agilent power products. For exam-
ple, common 3-phase voltages and
available options are shown in
table 4.