User`s guide
11
4.11 Recorder output
The recorder output on the 437B or 438A would
normally be used with manual ranging and pro-
duces an analog output level (0 to +1 volts) that is
proportional to the power level being measured.
This voltage level is scaled relative to the minimum
and maximum power levels for the current range.
The EPM series power meter has one continuous
range. Therefore, in order to be compatible with
the 437B or 438A, it is necessary to manually set
the EPM series power meter recorder minimum
and maximum power levels to suit the power
being measured (see the EPM series User’s Guide,
Chapter 2, “Recorder Output” section). It should
also be noted that the recorder output on the 437B
and 438A is permanently enabled, while on the
EPM series power meter it can be turned off. The
recorder output on the E4419A is also channel
selectable. The E4419B has two recorder outputs,
dedicated to each measurement channel.
4.12 Extensions to the 437B/438A command set
In addition to the 437B/438A command set, the
EPM series power meter in 437B/438A language
mode also accepts some extra commands, as
described below.
• Language selection: allows either SCPI or 437B/
438A language to be selected. This command is
accepted by both language modes and can also
be queried, whereby it will return either SCPI,
437B, or 438A.
Note: When changing language remotely, allow a
one-second delay before sending further remote
commands.
SYSTEM
LANGUAGE
SPACE SCPI
437B
438A
?
For E4418A/B
For E4419A/B