Specifications

Global Services North America
Wilmington MA 01887
Power Consumption:
Maximum Power: 4 KW
BTUs (Max): 13648.57
Power Requirements for the Anapurna M4F:
The following electrical requirements must be provided to your electrician.
Single phase, 208 Volts
40 Amp, 60Hz, dedicated circuit with ground, no neutral
The electrician must provide the proper power cord. (See Note 3)
The printer should have a twist lock plug/receptacle (L6-30 R/P). So that Agfa service can
disconnect power when needed.
Buck boost transformer wiring diagram is on page 10
Important
1. The printer operating voltage range is: 230 – 240 VAC, we need to increase the 208
Voltage to this range for the UV lamps to properly cure the ink. A Buck/Boost
transformer will be required to increase the 208 volts to this range. See pages 9,
10, and 11 for transformer data, configuration, and a sample transformer.
2. To minimize voltage loss the buck boost transformers should always be located
near the .
3. The length of the power cord should be 9 Feet plus the distance to the outlet or
power drop. The plug/receptacle should be a twist lock (Ex: Hubbell L6-30 P/R)
design in accordance with local electrical codes. Agfa Service will need to be able
to disconnect power when required.
If your electrician has any questions please contact AGFA at 1 800 879 2432
Questions? Contact 800-879-2432 and ask for an Anapurna Specialist
8