Specifications
Global Services North America
Wilmington MA 01887
Power Consumption:
Maximum Power: 4 KW
BTUs (Max): 13648.57
Power Requirements for the Anapurna M4F:
The following electrical requirements must be provided to your electrician.
• Single phase, 208 Volts
• 40 Amp, 60Hz, dedicated circuit with ground, no neutral
• The electrician must provide the proper power cord. (See Note 3)
• The printer should have a twist lock plug/receptacle (L6-30 R/P). So that Agfa service can
disconnect power when needed.
• Buck boost transformer wiring diagram is on page 10
Important
1. The printer operating voltage range is: 230 – 240 VAC, we need to increase the 208
Voltage to this range for the UV lamps to properly cure the ink. A Buck/Boost
transformer will be required to increase the 208 volts to this range. See pages 9,
10, and 11 for transformer data, configuration, and a sample transformer.
2. To minimize voltage loss the buck boost transformers should always be located
near the .
3. The length of the power cord should be 9 Feet plus the distance to the outlet or
power drop. The plug/receptacle should be a twist lock (Ex: Hubbell L6-30 P/R)
design in accordance with local electrical codes. Agfa Service will need to be able
to disconnect power when required.
If your electrician has any questions please contact AGFA at 1 800 879 2432
Questions? Contact 800-879-2432 and ask for an Anapurna Specialist
8