Outdoor Antenna Installation Guide A-7
The ring-terminal and ground wire are not included, but must
be installed by a certified electrician that is familiar with
national electricity & safety codes, according the instructions
described under “Grounding System” in Chapter 2.
4. Next insert the WaveACCESS Surge Arrester (item A” into the
bracket as pictured in Figure A-1 on page A-6.
5. Use the hex-nut (item F) to secure the WaveACCESS Surge
Arrester in its position, and ensure that the Protector is
properly connected to the grounding system.
!
WARNING:
To avoid damage to electronic equipment and your
WaveACCESS equipment always apply the
”WaveACCESS Surge Arrester” between the outdoor
antenna installation and the WavePOINT-II hardware or
other computing device that is connected to the outdoor
antenna(s).
Table A-4 Specifications Surge Arrester
Mechanical
Size
Height 69 mm (2.7 in.)
Diameter 26 mm (1 in.)
Weight 133 g (4.7 oz.)
Connectors
1
1 See also “Selecting the Correct Connector-Type” on page A-2
Standard-N (Male)
Operating Temperature - 40°C to +85°C
Electrical
Frequency Range 800-2500 MHz
Insertion Loss 0.2 dB
Surge Current 2000 Amp
Nominal Impedance 50 Ohms