Technical data

13
COMMISSIONING (CONTINUED)
7. Check burner pressure as follows:-
Repeat instruction 6 on completely cold cooker with the pressure gauge fitted to the burner
pressure test nipple (E). (See Fig. 2). Check that the burner pressure correctly
corresponds with the table marked ‘TECHNICAL DATA ‘, (page 7).
NOTE: IF FOR ANY REASON A GAS RATE CHECK IS REQUIRED. TURN OFF ALL OTHER
APPLIANCES USING GAS AND USING THE GAS METER TEST DIAL AND STOPWATCH.
CHECK THAT THE MAXIMUM GAS INPUT TO THE APPLIANCE IS AS INDICATED ON THE
DATA PLATE.
Once the correct setting has been confirmed, the heat control will operate automatically to
maintain the cooker at full temperature.
NOTE: REMEMBER TO NOTE THE SETTING POSITION IF TURNING OFF THE COOKER.
TO EXTINGUISH THE BURNER
Turn the gas valve control knob to the OFF position (See Fig. 8).
CHECK FOR CLEARANCE OF PRODUCTS OF COMBUSTION.
Ensure that all doors and windows of the room are closed.
Light the cooker as described. Leave on maximum rate for 5 minutes.
If there is a fan in the same room or nearby, then the spillage test must be repeated with the fan
turned on and any interconnecting doors between the cooker and the fan location open.
A spillage test must be carried out after 5 minutes as follows:
By holding a smoke match so that the match head is approximately 3mm up inside of the lower
edge of the draught diverter. Spillage is indicated by the smoke being displaced outwards from
the draught diverter. if in doubt repeat after a further 10 minutes.
If the spillage is detected the chimney may be faulty. The combustion discharge safety device
will have operated, the fault must be corrected before leaving the cooker installed, the device
must be depressed before the Aga can be re-lit.
If the fault cannot be corrected turn off and disconnect the gas supply to the cooker and seek
expert advice.
INSTRUCTIONS
Hand these and the operating instructions to the User for retention and instruct in the safe
operation of the appliance.
Finally advise the User that, for continued efficient and safe operation of the appliance it is
important that adequate servicing is carried out at regular intervals recommended by the AGA
Distributor or local Gas Region.