Technical data

SEE FIG. 22
Switch on the electricity supply.
Set the time clock as stated in the Users Instructions.
Turn the thermostat to max. allowing the burner to start. The
burner should go to lockout
Reset. Open the gas inlet cock, allowing the burner to
restart.
When the burner is in ‘run’ condition, close the inlet gas
cock. When the flame is extinguished the gas valves
solenoids on the burner should be de-energized almost
immediately.
The control will then allow one restart attempt and should
go to lockout after the expiry of the safety time.
Burner
TEST BURNER ON DRY RUN
(NO GAS)
FIG. 22
40
DESN 512346