Operation Manual
69
EN
IMDCFJ. 12.05 6343841_03
Dip-switch
No. dip
Status Function
A
1
ON
Machine set as heat pump
OFF
Machine set for cooling only
2
ON
Defrosting only by cycle reversal
OFF
Defrosting by hot gas injectio
n
3
ON
Glycol water: anti-freeze setting can be modified
OFF
Anti-freeze setting (parameter B) blocked
4
ON
Output control deactivated
OFF
Output control activated
5
ON
Safety capacity controls deactivated
OFF
Safety capacity controls activated
6
ON
Algorithm for check of low water content deactivated
OFF
Algorithm for check of low water content activated
7
ON
Condensation pressure control device present (accessory DCP)
OFF
Condensation pressure control device absent (accessory DCP)
8
ON
Configuration of the card for ANR unit (R407C)
OFF
Configuration of the card for ANL unit (R410A)
9
ON
Configuration of the card for inverter unit
OFF
Configuration of the card for ON/OFF chiller unit
10
ON
Configuration of the card for condenser unit
OFF
Configuration of the card for chiller unit
11
ON
Not used
OFF
Not used
12
ON
Not used
OFF
Not used
Dip-switch
Dip combinations
Function
DIP 1 DIP 2
B
OFF OFF
Factory settings
ON OFF
Factory settings
ON ON
Factory settings
OFF ON
Factory settings