Dip-switch (B)
Dip-switch (A)
Apart from the parameters that can be
inserted from the panel, the units are
fi tted with a series of dip-switches for
managing some options and functions
of the machine.
Remember that some of the options that
can be managed from the panel are
bound to a specifi c setting of some dip-
switches.
Table of DIP-SWITCH configuration
Default setting of MODUCONTROL DIP-SWITCH
Heat
recovery
unit
DIP-SWITCH (A) DIP-SWITCH (B)
1234567891011121 2
ANL OFF OFF OFF OFF ON OFF OFF OFF OFF OFF --- --- OFF OFF
ANL H ON OFF OFF OFF OFF OFF OFF OFF OFF OFF --- --- OFF OFF
ANL C ON OFF OFF OFF OFF OFF OFF OFF OFF ON --- --- OFF OFF
ANL A/Q ON OFF OFF ON ON ON OFF OFF OFF OFF --- --- OFF OFF
ANL HA/
HQ
ON OFF OFF ON OFF ON OFF OFF OFF OFF --- --- OFF OFF
ANL Z/Y ON OFF ON OFF OFF OFF OFF OFF OFF OFF --- --- OFF OFF
ANLI H ON OFF OFF OFF OFF OFF OFF OFF ON OFF --- --- ON OFF
ANR H ON OFF OFF OFF OFF OFF OFF OFF OFF OFF --- --- OFF OFF
ANR
HA/HK
ON OFF OFF ON OFF ON OFF ON OFF OFF --- --- OFF OFF
ANR HP ON OFF OFF OFF OFF OFF ON OFF OFF OFF --- --- OFF OFF
ANF H ON ON OFF OFF ON OFF OFF ON OFF OFF --- --- OFF OFF
ANF HA/
HK/HJ
ON ON OFF ON ON ON OFF ON OFF OFF --- --- OFF OFF
ANF HP ON ON OFF OFF ON OFF ON ON OFF OFF --- --- OFF OFF
ANK ON ON OFF OFF ON OFF OFF OFF OFF OFF --- --- OFF OFF
ANK Z/Y ON ON ON OFF OFF OFF OFF OFF OFF OFF --- --- OFF OFF
ANK A ON ON OFF ON ON ON OFF OFF OFF OFF --- --- OFF OFF
SRP ON ON OFF ON ON OFF OFF ON OFF OFF --- --- OFF OFF