Operation Manual

62
EN
IMDCFJ. 12.05 6343841_03
Air temperature limit 1
(*)
Index - String
MIN
value
MAX
value
Parameter function
-25°C 45°C
This parameter indicates the external air temperature at which the machine can produce
its maximum water value (this value is specified in parameter P - St1).
Water temperature limit 1
(*)
Index - String
MIN
value
MAX
value
Parameter function
0°C 70°C
This parameter indicates the maximum temperature of the water produced, in line with the outside air
temperature specified in parameter O - LA1.
Air temperature limit 2
(*)
Index - String
MIN
value
MAX
value
Parameter function
-25°C 45°C
This parameter indicates the external air temperature at which the machine can produc
e
its maximum
water value (this value is specified in parameter R - St2).
Water temperature limit 2
(*)
Index - String
MIN
value
MAX
value
Parameter function
0°C 70°C
This parameter indicates the maximum temperature of the water produced, in line with the outside air
temperature specified in parameter Q - LA2.
Maximum heating set point
Index - String
MIN
value
MAX
value
Parameter function
15°C 65°C
This parameter indicates the maximum temperature of the water produced by the unit in heat mode
.
Parameters only visible in model set for
hot water production
Parameters only visible in models set for
hot domestic water production
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor