Operation Manual

52
EN
IMDCFJ. 12.05 6343841_03
List of indexes and relative ADVANCED READINGS MENU readings
Index - String
Reading Meaning Notes
Inverter Current
Current (in Amperes) measured by the inverter module;
Parameter displayed with ANLI 21, 26, 40, 45, 71, 75, 80,100 only;
Inverter output voltage
Output voltage (in Volt) measured by the inverter module;
Parameter displayed with ANLI21, 26, 40, 45, 71, 75, 80,100 only;
BUS voltage
BUS voltage (in Volt) measured by the inverter module;
Parameter displayed with ANLI21, 26, 40, 45, 71, 75, 80,100 only;
Inverter dissipater temperature
Temperature (in C°) of the inverter module heat dissipater; Parameter dis-
played with ANL21, 26, 40, 45, 71, 75, 80,100 inverter only;
Value of the dynamic OFF force
Current dynamic ForceOff value calculated on the basis of the outdoor air
temperature
DHW remote probe value
Value read by the remote probe positioned in the plant water storage tank;
function enabled by the parameter (0) in the INSTALLER menu
Compressor intake probe value
Temperature read from the robe positioned on compressor intake.
Parameter displayed only with ANLI 21, 26, 40, 45, 71, 75, 80;
ADVANCED READINGS menu
To enter the ADVANCED READINGS
menu, press the key shown in (Fig.7).
Once the key has been pressed the
password must be inserted for access
to the various menus. To access the user
menu the password is 010. To modify
the value of the password use the arrow
keys. Once the correct password has
been inserted, press the key shown in
(Fig.7). The display shows the index of
the reading and a string of three char-
acters that identify it. The string remains
displayed for one second, after which it
is replaced by the value relative to the
reading itself. To pass to the next read-
ing, use the arrow keys (Fig.8).
Fig.7 Fig.8
PASSWORD = 010