Operation Manual

47
EN
IMDCFJ. 12.05 6343841_03
INSTALLER menu parameters (Password 030 )
Present on
the units
String
parameter
bAF tbF OAE Ati SCr Ad1 Bd1 AS1 LA1 St1 LA2 St2 LSP
Index
parameter
EFGH I JLNOPQRT
Unit
ANL 0 180 45 64 1 1 1 0 -15 43 -10 58 50
ANLI 0 180 45 64 1 1 1 0 -15 43 -10 58 55
ANR 0 180 45 64 1 1 1 0 -15 43 -10 58 55
ANF 0 180 45 64 1 1 1 0 -15 43 -10 58 55
ANK
0 180 45 65 1 1 1 0 -20 53 -10 62 60
SRPV1
0 180 45 58 0 1 1 0 -20 62 -10 65 63
SRA
0 180 45 58 0 1 1 0 -20 62 -10 65 63
WRL
--- --- --- ---
1
1 1 0 --- --- --- --- ---
Unit able to produce hot water (heat pump water or heating only unit)
All units (heat pumps, heating only or cooling only)
Unit that can produce domestic hot water
Functions relative to INSTALLER parameters
Index
String
Function
Index
String
Function
E - bAF
Enabling of flow switch by-pass
N - AS1
Enabling of supervisor writing
F - tbF
Flow switch by-pass time
O - LA1
Air temperature 1 limit
G - OAE
Outdoor temperature stand-by
P - St1
Water temperature 1 limit
H - Ati
High temperature return water
Q - LA2
Air temperature 2 limit
I - SCr
Screen saver configuration
R - St2
Water temperature 2 limit
J - Ad1
Supervisor modbus address
T - LSP
Maximum heating set-point limit that can be set
L - Bd1
Supervisor baudrate