MC2: 04/23/13 Page 140 of 144
GF-131
AERCO Control System (ACS)
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Installation, Operation, and Maintenance Manual
OMM-0081_0D
Table H-2: ACS Standard Holding Register Address Mapping - Continued
Modbus Data
Address
Decimal (Hex)
Menu Item Units and Range
Default/
Comments
112 (0x0070)
Net Boiler 21
Address
Address for Network Boiler 21 Default = 0
113 (0x0071)
Net Boiler 22
Address
Address for Network Boiler 22 Default = 0
114 (0x0072)
Net Boiler 23
Address
Address for Network Boiler 23 Default = 0
115 (0x0073)
Net Boiler 24
Address
Address for Network Boiler 24 Default = 0
116 (0x0074)
Net Boiler 25
Address
Address for Network Boiler 25 Default = 0
117 (0x0075)
Net Boiler 26
Address
Address for Network Boiler 26 Default = 0
118 (0x0076)
Net Boiler 27
Address
Address for Network Boiler 27 Default = 0
119 (0x0077)
Net Boiler 28
Address
Address for Network Boiler 28 Default = 0
120 (0x0078)
Net Boiler 29
Address
Address for Network Boiler 29 Default = 0
121 (0x0079)
Net Boiler 30
Address
Address for Network Boiler 30 Default = 0
122 (0x007A)
Net Boiler 31
Address
Address for Network Boiler 31 Default = 0
**123 (0x007B)
Net Boiler 32
Address
Address for Network Boiler 32 Default = 0
124 (0x007C) Network Baud
0=2400, 1=4800, 2=9600, 3=14400,
4=19200
2 = 9600
125 (0x007D) Network Timeout 5 to 240 sec
Default = 60
sec.
126 (0x007E)
Password Lo
0 to 255 (73)
Default = 0
127 (0x007F)
Password Hi
0 to 255 (79)
Default = 0
128 (0x0080)
Modbus Control
Type
0 = Round-Robin
1 = Broadcast
Default = 0
(Round Robin)
129 (0x0081) Modbus Pass-Thru
0 = Disabled
1 = Enabled
Default = 0
(Disabled)
130 (0x0082)
RESERVED
Only for BMS II