CHAPTER 3 – OPERATION
Page 46 of 196 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0098_0A
04/01/2014 Ph.: 800-526-0288 GF-144
The Items contained in group 1 (BST Monitor Items) are ALWAYS displayed within the menu,
as these items are critical for proper system operation. Therefore, the BST Monitor Items
Header itself is NOT displayed.
The Items contained in groups 2-5 are NOT DISPLAYED unless that particular item group has
been enabled from the C-More keypad.
Table 3-7: BST Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
BST Mode
Off BST Slave BST Master Off
BST Setpoint BST Setpt Lo Limit BST Setpt Hi Limit 130°F
Header Temp NA
Header Temp
(°F)
BST Fire Rate 0 100% Fire rate %
BST Ave Fire Rate 0 100% Avg Fire Rate %
BST Outdoor Temp NA
Outdoor Temp
(°F)
Units Available
0
8
Units Present
Units Ignited
0
8
Units firing
BST Valve State 0 (CLOSED) 1 (OPEN) 0
1 Comm Errors 8 0 9 0
1 BST Units 8
0 (see table)
0 (see table)
0
*BST SETUP MENU*
Disabled Enabled Disabled
BST Setpoint Mode Constant Setpoint Remote Setpoint Outdoor Reset Constant Setpt
Head Temp Source
Network
FFWD Temp
FFWD Temp
Header Temp Addr
0
255
240
Header Temp Point 0 255 14
BST Outdoor Sens Disabled Enabled Disabled
Outdr Tmp Source
Outdoor Temp
Network
Outdoor Temp
Outdoor Tmp Addr
0
255
240
Outdoor Tmp Pnt 0 255 215
BST Remote Signal 4-20 mA/1-5 Vdc;
0-20 mA/0-5
Vdc;
Network Network
BST Auto Mstr No
Yes
NOTE! A Modbus temperature
transmitter must be installed in
conjunction with this feature.
No
BST Auto Timer
10 sec
120 sec
30 sec
Remote Intlk Use Boiler Shutdown System Shutdown
System
Shutdown
One Boiler Mode Off
On-Outlet
Temp
On-Avg Temp Off
1 Blr Threshold
10
35
25
Setpoint Setback Disable Enable Disable