User Manual

GF-123 Benchmark 2.0LN Low NOx Boiler Chapter 4
OMM-0046_0F Installation, Operation and Maintenance Manual Initial Start-Up
PR1 10/17/12 AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 Page 61 of 172
41. Once the oxygen level is within the specified range at 45%, press the ENTER key to store
the selected blower output voltage for the 45% valve position.
42. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
43. Press the CHANGE key. SET Valve Position will begin to flash.
44. Press the ▼ arrow key until the SET Valve Position reads 30%, then press the ENTER key.
45. Press the ▼ arrow key until CAL Voltage 30% is displayed.
46. Press the CHANGE key. CAL Voltage 30% will begin to flash.
47. The oxygen level at the 30% valve position should be as shown below. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-11: Combustion Oxygen Level at
30%
Valve Position
Oxygen %
± 0.2
Carbon Monoxide NOx
8.0 %
<50 ppm
<30 ppm
48. If the oxygen level is not within the specified range, adjust the level using the and
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
49. Once the oxygen level is within the specified range at 30%, press the ENTER key to store
the selected blower output voltage for the 30% valve position.
50. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
51. Press the CHANGE key. SET Valve Position will begin to flash.
52. Press the ▼ arrow key until the SET Valve Position reads 20%, then press the ENTER key.
53. Press the ▼ arrow key until CAL Voltage 16% is displayed.
54. Press the CHANGE key. CAL Voltage 20% will begin to flash.
55. The oxygen level at the 20% valve position should be as shown below. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-12: Combustion Oxygen Level at
20%
Valve Position
Oxygen %
± 0.2
Carbon Monoxide NOx
8.6 %
<50 ppm
<30 ppm
56. If the oxygen level is not within the specified range, adjust the level using the and
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
57. Once the oxygen level is within the specified range at 20%, press the ENTER key to store
the selected blower output voltage for 20% valve position.
58. This completes the Propane Combustion Calibration procedure.