GF-123 Benchmark 2.0LN Low NOx Boiler Chapter 4
OMM-0046_0F Installation, Operation and Maintenance Manual Initial Start-Up
PR1 10/17/12 AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 Page 59 of 172
Table 4-7: Combustion Oxygen Levels for a
100%
Valve Position
Oxygen %
± 0.2
Carbon Monoxide
NOx
4.8 %
<100 ppm
<100 ppm
14. If necessary, adjust the iris air damper shown in Figure 4-4 until the oxygen level is within
the range specified in Table 4-2.
15. Once the oxygen level is within the specified range at 100%, lower the valve position to
80%.
NOTE
The remaining combustion calibration steps are performed using the
Combustion Cal Menu included in the C-More Control System. The
combustion calibration control functions will be used to adjust the oxygen
level (%) at valve positions of 80%, 60%, 45%, 30% and 20% as described
in the following steps. These steps assume that the inlet air temperature is
within the range of 50°F to 100°F.
16. Press the MENU key on the front panel of the C-MORE and access the Setup menu. Enter
password 6817 and then press the ENTER key.
17. Press the MENU key on the front panel of the C-MORE until Combustion Cal Menu appears
on the C-More display.
18. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
19. Press the CHANGE key. SET Valve Position will begin to flash.
20. Press the ▲ arrow key until the SET Valve Position reads 80%. Press the ENTER key.
21. Next, press the down (▼) arrow key until CAL Voltage 80% is displayed.
22. Press the CHANGE key and observe that CAL Voltage 80% is flashing.
23. The oxygen level at the 80% valve position should be as shown below. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-8: Combustion Oxygen Level at
80%
Valve Position
Oxygen %
± 0.2
Carbon Monoxide NOx
5.0 %
<100 ppm
<30 ppm
24. If the oxygen level is not within the specified range, adjust the level using the and
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the arrow key increases the oxygen level and pressing the down
arrow key decreases the oxygen level.
25. Once the oxygen level is within the specified range at 80%, press the ENTER key to store
the selected blower output voltage for the 80% valve position.