GF-123 Benchmark 2.0LN Low NOx Boiler Chapter 4
OMM-0046_0F Installation, Operation and Maintenance Manual Initial Start-Up
PR1 10/17/12 AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 Page 57 of 172
48. If the oxygen level is not within the specified range, adjust the level using the and
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
49. Once the oxygen level is within the specified range at 30%, press the ENTER key to store
the selected blower output voltage for the 30% valve position.
50. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
51. Press the CHANGE key. SET Valve Position will begin to flash.
52. Press the ▼ arrow key until the SET Valve Position reads 16%, then press the ENTER key.
53. Press the ▼ arrow key until CAL Voltage 18% is displayed.
54. Press the CHANGE key. CAL Voltage 18% will begin to flash.
55. The oxygen level at the 18% valve position should be as shown below. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-6: Combustion Oxygen Levels for a 18% Air/Fuel Valve Position
Oxygen %
± 0.2
Carbon Monoxide NOx
8.0 %
<50 ppm
<30 ppm
56. If the oxygen level is not within the specified range, adjust the level using the and
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
57. Once the oxygen level is within the specified range at 16%, press the ENTER key to store
the selected blower output voltage for the 16% valve position.
58. This completes the Natural Gas Combustion Calibration procedure.