User Manual

Chapter 4 Benchmark 2.0LN Low NOx Boiler GF-123
Initial Start-Up Installation, Operation and Maintenance Manual OMM-0046_0F
Page 56 of 172 AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 10/17/12
31. The oxygen level at the 60% valve position should be as shown below. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-3: Combustion Oxygen Levels for a 60% Air/Fuel Valve Position
Oxygen %
± 0.2
Carbon Monoxide NOx
5.7 %
<50 ppm
<30 ppm
32. If the oxygen level is not within the specified range, adjust the level using the and
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
33. Once the oxygen level is within the specified range at 60%, press the ENTER key to store
the selected blower output voltage for the 60% valve position.
34. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
35. Press the CHANGE key. SET Valve Position will begin to flash.
36. Press the ▼ arrow key until the SET Valve Position reads 45%, then press the ENTER key.
37. Press the ▼ arrow key until CAL Voltage 45% is displayed.
38. Press the CHANGE key. CAL Voltage 45% will begin to flash.
39. The oxygen level at the 45% valve position should be as shown below. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-4: Combustion Oxygen Levels for a 45% Air/Fuel Valve Position
Oxygen %
± 0.2
Carbon Monoxide NOx
7.2 %
<50 ppm
<30 ppm
40. If the oxygen level is not within the specified range, adjust the level using the and
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.
41. Once the oxygen level is within the specified range at 45%, press the ENTER key to store
the selected blower output voltage for the 45% valve position.
42. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
43. Press the CHANGE key. SET Valve Position will begin to flash.
44. Press the ▼ arrow key until the SET Valve Position reads 30%, then press the ENTER key.
45. Press the ▼ arrow key until CAL Voltage 30% is displayed.
46. Press the CHANGE key. CAL Voltage 30% will begin to flash.
47. The oxygen level at the 30% valve position should be as shown in Table 4-5. Also, ensure
that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.
Table 4-5: Combustion Oxygen Levels for a 30% Air/Fuel Valve Position
Oxygen %
± 0.2
Carbon Monoxide NOx
8.0 %
<50 ppm
<30 ppm