GF-123 Benchmark 2.0LN Low NOx Boiler Chapter 3
OMM-0046_0F Installation, Operation and Maintenance Manual Operation
PR1 10/17/12 AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 Page 43 of 172
Table 3-6: Combustion Cal MenuNatural Gas
Table 3-7: Combustion Cal MenuPropane
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
CAL Voltage 18%
.25 10.0v 1.00v
CAL Voltage 30%
.25 10.0v 2.30v
CAL Voltage 45%
.25 10.0v 2.95v
CAL Voltage 60%
.25 10.0v 3.60v
CAL Voltage 80%
.25 10.0v 5.30v
CAL Voltage 100%
.25 10.0v 9.10v
SET Valve Position
0% 100% 0%
Blower Output
Monitor Blower Output
Voltage
.00v
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
CAL Voltage 20%
.25 10.0v 1.10v
CAL Voltage 30%
.25 10.0v 1.95v
CAL Voltage 45%
.25 10.0v 3.00v
CAL Voltage 60%
.25 10.0v 3.00v
CAL Voltage 80%
.25 10.0v 4.45v
CAL Voltage 100%
.25 10.0v 8.20v
SET Valve Position
0% 100% 0%
Blower Output
Monitor Blower Output
Voltage
.00v