User Manual
Appendix E Benchmark 2.0LN Low NOx Boiler GF-123
Default Settings Installation, Operation and Maintenance Manual OMM-0046_0E
Page 134 of 172 AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 10/17/12
APPENDIX E: BOILER DEFAULT SETTINGS
Table E-1: Boiler Default Settings
MENU & OPTION FACTORY DEFAULT
Setup Menu
Password 0
Language English
Unit of Temp Fahrenheit
Comm Address 0
Baud Rate 9600
Configuration Menu
Internal Setpt 130°F
Unit Type BMK Boiler LN
Unit Size 2000 MBH (2.0 MBTU)
Fuel Type Natural Gas
Boiler Mode Constant Setpoint
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Setpt Lo Limit 60°F
Setpt Hi Limit 195°F
Temp Hi Limit 195°F
Max Valve Position 100%