3.6 CONFIGURATION MENU
The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the valid password has been entered. Setpt is
required for operation in the Constant Setpoint mode. The remaining options in this menu
require the valid password to be entered, prior to changing existing entries. This menu
contains a number of other configuration settings which may or may not be displayed,
depending on the current operating mode setting.
NOTE
The Configuration Menu settings shown in Table 3-4 are Factory-Set in accordance with the
requirements specified for each individual order. Therefore, under normal operating
conditions, no changes will be required.
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Internal Setpt Lo Temp Limit Hi Temp Limit 130°F
Unit Type KC Boiler, KC Boiler LN,
BMK Boiler, BMK Boiler LN,
BMK Boiler Dual, KC Water
Heater, KC Water Heater LN,
Water Heater 2010
BMK Boiler
LN
Unit Size 0.5 MBTU, 1.0 MBTU
1.5 MBTU, 2.0 MBTU
3.0 MBTU, 3.5 MBTU
4.0 MBTU, 5.0 MBTU
6.0 MBTU
2.0 MBTU
Fuel Type Natural Gas, Propane Natural Gas
Boiler Mode Constant Setpoint,
Remote Setpoint,
Direct Drive
Combination
Outdoor Reset
Constant
Setpoint
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)
4 20 mA/1 5V
0 -20 mA/0 5V
PWM Input (BMS)
Network
4 20 mA,
1-5V
Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F 230°F 70°F