Owner manual

CHAPTER 4: INITIAL START-UP
Page 52 of 160 PR2: 04/22/13
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
Operation and Maintenance Manual
OMM-0052_0E
GF-127
AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Ph: 800-526-0288
40. The oxygen level at the 45% valve position should be as shown below. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-10: Combustion Oxygen Level at
45%
Valve Position
Oxygen %
± 0.2
Carbon Monoxide
NOx
7.0 %
<100 ppm
<100 ppm
41. If the oxygen level is not within the specified range, adjust the level using the and arrow
keys. This will adjust the output voltage to the blower motor as indicated on the display.
Pressing the arrow key increases the oxygen level and pressing the arrow key
decreases the oxygen level.
42. Once the oxygen level is within the specified range at 45%, press the ENTER key to store the
selected blower output voltage for the 45% valve position.
43. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
44. Press the CHANGE key. SET Valve Position will begin to flash.
45. Press the ▼ arrow key until the SET Valve Position reads 30%, then press the ENTER key.
46. Press the ▼ arrow key until CAL Voltage 30% is displayed.
47. Press the CHANGE key. CAL Voltage 30% will begin to flash.
48. The oxygen level at the 30% valve position should be as shown below. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.
Table 4-11: Combustion Oxygen Level at
30%
Valve Position
Oxygen %
± 0.2
Carbon Monoxide
NOx
7.9 %
<100 ppm
<100 ppm
49. If the oxygen level is not within the specified range, adjust the level using the and arrow
keys. This will adjust the output voltage to the blower motor as indicated on the display.
Pressing the arrow key increases the oxygen level and pressing the arrow key
decreases the oxygen level.
50. Once the oxygen level is within the specified range at 30%, press the ENTER key to store the
selected blower output voltage for the 30% valve position.
51. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
52. Press the CHANGE key. SET Valve Position will begin to flash.
53. Press the ▼ arrow key until the SET Valve Position reads 21%, then press the ENTER key.
54. Press the ▼ arrow key until CAL Voltage 21% is displayed.
55. Press the CHANGE key. CAL Voltage 21% will begin to flash.
56. The oxygen level at the 21% valve position should be as shown below. Also, ensure that the
carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.