Specifications
Page 8 of 40 12/03/2013
Benchmark Series Boilers
Venting and Combustion Application Guide
GF-2050
TAG-0022_0S
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Figure 2: All Combustion Air from Adjacent Indoor Spaces through Indoor
Combustion Air Openings
1.6 Combustion Air from OUTSIDE the Building
Outdoor combustion air shall be provided through opening(s) to the outdoors in accordance with
the methods described below. The minimum dimension of air openings shall not be less than
3 inches (80 mm). The required size of the openings for combustion air shall be based upon the
net free area of each opening. When the free area through a louver, grille, or screen is known, it
shall be used to calculate the opening size required to provide the free area specified. For
additional details, consult NFPA 54, or in Canada, CSA B149.1-10, paragraphs 8.4.1 and 8.4.3.
1.7 Two-Permanent-Openings Method (USA Only)
Two permanent openings shall be provided; one commencing within 12 inches (300 mm) of the
top of the enclosure and one commencing within 12 inches (300 mm) of the bottom. The
openings shall communicate directly ― or by ducts ― with the outdoors, or spaces that freely
communicate with the outdoors, as show on the following pages:
1. When communicating directly with the outdoors, or when communicating to the outdoors
through vertical ducts, each opening shall have a minimum free area of 1 inch
2
per
4,000 BTU/hr (550 mm
2
/kW) of total input rating of all appliances in the space (see
Figures 3 and 4).