Specifications
GF-2030 Benchmark Series Boilers
TAG-0047_0G Gas Supply Design Guide
PR1 10/04/13 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 5 of 10
Diagram 1. Single Boiler Gas Pipe Connections (BMK 2000 Shown)
CUSTOM GAS TRAINS
Some utilities, insurance carriers, and industrial customers have special requirement gas components on high input
devices beyond that which are normally supplied with AERCO boilers. Secondary shutoffs, high or low pressure
operators, and external regulators are typical of the requirements of gas utilities. It is mandatory that a designer or
installer comply with these requirements. AERCO assumes no liability when these requirements are not satisfied for
any location or installation. Contact your local gas utility for their specific requirements before installing AERCO
equipment. Special gas trains with a double block and bleed (DBB) configuration (formerly IRI) are available from
AERCO.
The minimum gas inlet pressure requirements for natural gas (N.G.) and propane (LPG) are as follows:
Minimum Gas Inlet Pressure Requirements for Natural Gas and Propane
BMK 750
BMK 1000
BMK 1500
BMK 2000
BMK 2500
BMK 3000
BMK 6000
Gas Train
N.G.
LPG
N.G.
LPG
N.G.
LPG
N.G.
LPG
N.G.
LPG
N.G.
LPG
N.G.
LPG
DBB (IRI)
4.5”
W.C.
7”
W.C.
4.5”
W.C.
10”
W.C.
4.5”
W.C.
---
5.0”
W.C.
5.0”
W.C.
4.5”
W.C.
4.5”
W.C.
4.5”
W.C.
4.5”
W.C.
14”
W.C.
10.5”
W.C.
Dual Fuel
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
4”
W.C.
8”
W.C.
14”
W.C.
10.5”
W.C.
Dual Fuel
DBB (IRI)
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
4”
W.C.
8”
W.C.
14”
W.C.
10.5”
W.C.
MANUAL
SHUTOFF
VALVE
GAS
PRESSURE
REGULATOR
NATURAL
GAS
SUPPLY
(Required for
Massachusetts
installations)