5.7 Diagnostics – Blocking (Err) Errors
Blocking errors are generated by a permanent fault. There is no way to unlock the unit other
than to resolve the cause of the fault.
To reset a lockout error, do the following:
Resetting the Unit after a Lockout Error
1. When the boiler goes into lockout, the icon will show in the control panel display and
the burner icon(s) ( , , , or ) associated with the lockout will blink.
2. Press the
RESET button once and the lockout error number will show in the display.
3. To resolve the error, consult the table of Error (Err) messages in Figure 5-8 and attempt to
diagnose and resolve the problem.
4. To return the display to normal function, press and hold down the
RESET button for at least
5 seconds.