1.4.3 Dependent Boiler
Dependent Boiler Parameters
Holding
Register
Access
Parameter Name
Automatic
Conversion
Range
R
W
100
0064 X X Modbus Units - Bit0: °C / °F Bit1: bar / psi
101
0065
X
-
Device type
-
2 = Dependent Boiler
102
0066 X - State - See state table
103
0067 X - Status - See status table
104
0068 X - Error Code - See error list
105
0069 X - Warning Code - See warning list
106
006A X X Boiler CH setpoint V Depending on units °C / °F
107
006B X X Boiler DHW setpoint V Depending on units °C / °F
108
006C X X
Boiler operation
- 0..x
109
006D X X
DHW type
- 0..x
110
006E X X CH mode - 0..x
111
006F X X DHW mode - 0..x
112
0070 X - Supply temperature V Depending on units °C / °F
113
0071 X - Return temperature V Depending on units °C / °F
114
0072 X - DHW temperature V Depending on units °C / °F
115
0073 X - Flue gas temperature V Depending on units °C / °F
116
0074 X -
Heat exchanger
temperature
V Depending on units °C / °F
117
0075 X - Firing Rate V 0..100%
118
0076 X - Min Firing Rate 0..100%
119
0077 X - Flame current V 0..x uA
120
0078 X - Water pressure V Depending on units 0..x bar/psi
121
0079 X - Analog in V 0..10,0V
122
007A X - Analog out V 0..10,0V
123
007B X -
Information:
(optionally implemented)
-
Bit0: On/Off - Flame Signal
Bit1: Ok/Nok - Water level
Bit2: Ok/Nok - Low gas pressure
Bit3: Ok/Nok - High gas
pressure
Bit4: On/Off - Air pressure
Bit5: Ok/Nok - Blocked flue
Bit6: On/Off - Air damper Bit7:
124
007C X - CH pump V 0/100 or 0..100%
125
007D X - DHW pump V 0/100 or 0..100%
126
007E X - Ignition count OK - 0..65536, resolution 16