Specifications
Engineering Specification
Page 11
Properties
Size
1
Min Value
0
Format
Unsigned Integer
Max Value
255
Read-only
Fasle
Default Value
0
Altering capabilities
Fasle
Advanced
Fasle
Description
Value
Function
0~255
Basic Set Value
Parameter
0x0D (13)
Name
Offset value for Mould danger alarm
Info
Increase the humidity threshold.
Properties
Size
1
Min Value
0
Format
Unsigned Integer
Max Value
10
Read-only
False
Default Value
0
Altering capabilities
False
Advanced
False
Description
The default Relative Humidity to trigger Mould dangter alram is 70%.
Value
Function
0-10
0%-10%
Parameter
0x0E (14)
Name
Offset value for Temperature
Info
Calibrate temperature when checked
Properties
Size
2
Min Value
-200
Format
Unsigned Integer
Max Value
200
Read-only
False
Default Value
0
Altering capabilities
False
Advanced
False
Description
Scale is defined by Param 64.eg: Value 15 means 1.5 °C or 1.5F
Value
Function
-200~200
-20~20 degrees
Parameter
0x0F (15)
Name
Offset value for Humidity
Info
Calibrate humidity when checked
Properties
Size
1
Min Value
-50
Format
Unsigned Integer
Max Value
50
Read-only
False
Default Value
0
Altering capabilities
False
Advanced
False
Description
Value
Function
-50~50
-50~50%
Parameter
0x10 (16)
Name
Check interval for parameter 5,6,7 and 8
Info
Set the interval time
Properties
Size
1
Min Value
1