DOOR FORCED OPEN WARNING & TIMING (Location 80)
(1) LOCATION
Key in Location
(2) FUNCTION MODES FOR DOOR FORCED OPEN WARNING
The Door Forced Open Warning function works with a Door Position Sensing switch equipped on the
door (usually a magnetic contact). Once a Timing Figure is put into the Function Mode box, the
warning mode is enabled.
--- Door Forced Open Warning OFF – (Default)
-  --- Door Forced Open Warning & Alarm Enabled & Timing
The Timing Figure for the Warning can be 1-999 seconds. The keypad generates the door forced
open warning beeps and activates the alarm output (Terminal 13) instantly if the door is forced to
open without a valid User Code/Card or pressing of Egress Button. The beeps and alarm will last as
long as the time set on the timer and it can be stopped at anytime with an User Code/Card in Group
1 before the end of the time.
The Manner of The Door Forced Open Warning:
a) The door is forced to open (without using Code/Card or Egress Button) – Warning & Alarm
b) The door is opened with Code/Card – No Warning or Alarm
c) The door is opened with Egress Button – No Warning or Alarm
(3) VALIDATION
Press key once. Two-beep confirms the entry
DOOR PROPPED-UP WARNING & THE DELAY TIME (Location 81)
(1) LOCATION
Key in Location
(2) FUNCTION MODES FOR DOOR PROPPED-UP WARNING
If somebody opened the door and left it open longer than the allowable delay time, the keypad will
generate door propped-up warning until the door is re-closed. There is warning beeps from the
keypad only but it does not activate the alarm output. This function works with a door position
sensing switch equipped on the door.
--- Door Propped-up Warning OFF – (Default)
-  --- Door Propped-up Warning ON & The Delay Time
The Delay Time can be 1 to 999 seconds. It is the allowed time for door open without starting
warning.
(3) VALIDATION
Press key once. Two-beep confirms the entry



FUNCTION MODES
VALIDATIONLOCATION
or
-


(2) (3)(1)
FUNCTION MODES VALIDATIONLOCATION
or
-
 
(2) (3)(1)


START & STOP TIMES FOR DAILY INHIBITION OF OUTPUT 1 (Location 56)
Setting with start and stop times into the keypad, the real-time inhibition period for output 1 will
recycle daily until the time settings are cleared.
This function works with the real-time-clock. Set up the real-time at Location 55 is necessary.
For safety reason, the Egress Button is designed always valid. The door lock (controlled by output
1) can be opened with it at anytime during inhibition.
(1) LOCATION
Key in Location
(2) START TIME
– Set the real-time inhibition starting time in Hour and Minute. The allowed time
figure is 00:00 – 23:59
The starting time is based on 24 hours daily with the first two digits for hours and the last two digits
for minutes. The time in second always starts at 0 0.
(3) STOP TIME
– Set the real-time inhibition stopping time in Hour and Minute. The allowed time
figure is 00:00 – 23:59
The stopping time is based on 24 hours daily with the first two digits for hours and the last two digits
for minutes. The time in second always starts at 0 0.
(4) VALIDATION
Press key once.
Two-beep confirms the setting.
STOP TIME
START TIME VALIDATIONLOCATION

(4)
(3)
 
HOURS MINUTES
(2)
(1)
 
HOURS MINUTES

 
 
