Operating instructions
30
The default settings of the potentiometer can be taken from the following
table.
Tab. 5 Default values potentiometer
Setting
Chapter
No.
3.2.1
DefaultPhase angle 1. half wave act. Setting
Thyro-A 1A: 60° el.
Thyro-A 2A: 90° el.
R201
All standard settings should be checked by the user as a matter of course and adju-
sted to the operating conditions (e.g. operating mode, control mode, limits, monito-
ring, control characteristics, actual value output, fault indications etc.)
REMARK
Apart from the load and current supply to X1.1, certain control signals
must be connected too. The following signals are essential for opera-
ting the device:
Set point (terminal 4 or by system interface)
Pulse lock (on ground, on terminal 1,2; jumper)
If the pulse lock jumper is not connected, the device is in a locked state and will not
operate. Communication via interface is still possible. Further details on the pulse
lock are described in the chapter of the same name.
ATTENTION
Heat sinks and neighbouring plastic parts are hot during operation
( 70°C)! Provided sign should be fixed nearby Thyro-A.
8.3 Service
The devices delivered have been produced under quality standard ISO 9001.
Should nevertheless faults or problems occur, our
24-hour service hotline: Tel: 02902 / 763-100.
is at your service.