UPS Status Hex-Value Description
UPS_SB_BYPASS_MODE 0x0001 power piped thru
UPS_SB_SHUTDOWN 0x0002 shutdown ups
UPS_SB_OUTPUT_ACT 0x0004 inverter on
UPS_SB_BACKUP_MODE 0x0008 battery power
UPS_SB_BATTERY_LOW 0x0010 low battery err
UPS_SB_OVER_TEMP 0x0020 over temp err
UPS_SB_TEST_ACT 0x0040 test in progress
UPS_SB_INPUT_HIGH 0x0080 over power err
UPS_SB_OUTPUT_HIGH 0x0100 over load err
UPS_SB_INVERTER_FAILURE 0x0200 Inverter error
UPS_SB_BATTERY_BAD 0x0400 Battery error
UPS_SB_ECO_MODE 0x0800 eco - bypass
UPS_SB_INVERTER_WARN 0x1000 eco - bypass
UPS_SB_UPS_FAILED 0x2000 prser flag
UPS_SB_COMM_LOST 0x4000 for snmp
UPS_SB_DVG_ALARM 0x8000 SiteManager/SiteMonitor
D.6. Bus termination
It is necessary to set the last bus device on the RS-485 Bus jumper for the bus termination.
The jumper is already set in newly delivered adapters. Please remove the 4 screws at the
underside of the adapter in order to open the box. You will find the jumper J1 near the network
connector. Default is ON = CS121 is last device. If you take off the Jumper, then the CS121
can be used inside a group of chained devices.
D.7. Configuration
Please use Telnet (network connection) for the configuration with the default IP address
10.10.10.10. Put DIP switch 1 into the “OFF” position. If you have a RS-232/ RS-485 converter
available you can also use a HyperTerminal via COM2 with both DIP switches in the “OFF”
position.
D.8. TCP/IP - UDP Ports
The following are ports of the CS121 SNMP Adapter. These are the ports that have to be
made available in the Firewall in order to use all of the CS121 functions:
Echo 7/tcp
echo 7/udp
ftp-data 20/tcp
ftp 21/tcp
telnet 23/tcp
smtp 25/tcp
http 80/tcp