User manual
72
Section OEM RITTAL
Digital Input Status(DI)
0 bit 2 Bypass working Status 0: Normal, Status 1: Alert 1
1 bit 2 Bypass Interruption Status 0: Normal, Status 1: Alert 1
2 bit 2 Rectifier Failure Status 0: Normal, Status 1: Alert 1
3 bit 2 Inverter Failure Status 0: Normal, Status 1: Alert 1
4 bit 2 Over Temperature Status 0: Normal, Status 1: Alert 1
5 bit 2 Over Load Status 0: Normal, Status 1: Alert 1
6 bit 2 0 Status 0: Normal, Status 1: Alert 1
7 bit 2 Battery Voltage too Low Status 0: Normal, Status 1: Alert 1
8 bit 2 Fuse broken Status 0: Normal, Status 1: Alert 1
9 bit 2 Battery discharging Status 0: Normal, Status 1: Alert 1
10 bit 2 0 Status 0: Floating charge
Status 1: Instant charging
1
11~3
0
bit 2 For future expansion 1
A
fter
31
bit 2 Venders own definition 1
A
nalog Measurement point(AI)
00 word 4 R phase input voltage 0.1 Volt 2
01 word 4 S phase input voltage 0.1 Volt 2
02 word 4 T phase input voltage 0.1 Volt 2
03 word 4 R phase input current 0.1A 2
04 word 4 S phase input current 0.1A 2
05 word 4 T phase input current 0.1A 2
06 word 4 Input frequency 0.1Hz 2
07 word 4 R phase output voltage 0.1 Volt 2
08 word 4 S phase output voltage 0.1 Volt 2
09 word 4 T phase output voltage 0.1 Volt 2
10 word 4 R phase out current 0.1A 2
11 word 4 S phase output current 0.1A 2
12 word 4 T phase output current 0.1A 2
13 word 4 Output frequency 0.1Hz 2
14 word 4 Battery voltage 0.1 Volt 2
15 word 4 0 0.1A 2
16 word 4 Battery temperature#1 0.1deg C 2
21~3
1
word 4 For future expansion 2
A
fter
32
word 4 Vender self definition
Digital output(DO)
Function 1 to read data; 5 to control the function
0 bit 1 / 5 UPS Turn On
1 bit 1 / 5 UPS Shut down
2 bit 1 / 5
A
larm Reset
3 bit 1 / 5 Battery Instant Charging
4 bit 1 / 5 Battery Floating Charging
5~10 bit For future expansion
A
fte
r
Vender self definition
Other OEM’s ->See OEM MODBUS Documentation
UPSMAN Status Bytes - Standard Device Status Bits