6.3 SENSORMANAGER
6.3.1 General information
If more than 1 or 2 environmental values are wanted to manage, than the SENSORMANGER
(SensorMan) is your choice. This device is a data measurement and collecting unit which
allows the individual measurement and monitoring of 8 analog measurement devices (0-10V)
and 4 digital alarm inputs or 4 outputs (open collectors).
Figure 56: Sensor Manager (SensorMan)
The SENSORMANAGER is a system extension for the CS121 series or for a Windows PC:
Universal Remote Sensor Control Box for the monitoring of temperature, humidity and many
other types of sensors as well as for the the management of digital input/output signals. 8
analog inputs (0-10V), + 4 digital input and/or outputs (48 V 500mA). Digital Outputs are
configurable as normally open or as normally closed. Digital input connections directly through
sensor for some models or connect directly to the RJ11 socket. Convenient splitting plug
available for attaching two sensors to one RJ11 socket.
Purpose:
• Monitoring of temperatures, humidity and other analog data in computer rooms with
automated response to system alarms.
• Alarms can be individually configured and defined for trip contacts such as fire, smoke and
intrusion, and minimum/maximum thresholds values can be set for analog devices such as
humidity, temperature and pressure, fluid level, etc. – any sensor which transmits its values
between 0- 10 V may be connected to a SENSORMANAGER.
• Data logging, logging of alarms, automatic shutdowns of network computers, and other
actions can be set as reactions to critical alarms.
• All system operating and configuring can be done remotely via Web browser. The EVENT
driven alarm management system of the CS121 informs the administrator of problems and
may automatically switch off computers and other devices (Optional extensions: SITESWITCH
4 or SITEMANGER).
• The SENSORMANAGER is an extension to the CS121 Webmanager. If you want to connect
any other computing device, please download the RS-232 protocol for the SENSOR
MANAGER from our website and adjust your software to this communication type.
Important:
The SENSORMANAGER is compatible to the former TEMPMAN MI4. Users wishing to
manage more than 4 temperatures must update the CS121 to Firmware 2.53 or higher. New
firmware for your CS121 is available for download at: http://www.generex.de