Figure 17: HTTP - UPS Model & System
With the parameters UPS ID, system-name, -location, -contact you can describe the UPS and
CS121. This is useful e.g. to locate the UPS physically and can be used among others for
event settings.
Note: Do not change the default UPS-Parameters for Baud Rate and Hold time
unless you have special instructions from the UPS maker.
Please note the field “System Shutdown Time “: This value determines how many minutes
before a complete battery unload the event “System shutdown” from the event menu (please
cp. according section 3.2.5 Events / Alarms) is executed. Attention: This EVENT is the final
task a CS121 can initiate before the UPS switches off ! DO NOT use this Event for triggering
shutdowns via RCCMD etc. because the remaining time in this status is not secure. We
strongly recommend to use the Event Powerfail and configure the RCCMD shutdown calls with
a UPS “remaining time”, this is the best way to send RCCMD shutdowns to several IP
addresses in a certain logic or sequence!
Note: Please apply your changes before leaving the menu to send the values
to the CS121-adapter - do not forget to press “SAVE & EXIT &
REBOOT” after you have finished your configuration work!
The section „Custom Values“ contains 6 fields with can be used to save custom specific
comments concerning your UPS.