Finally, check the firm seating of the wire jumpers attached in the
Emergency Power Off plug and tighten the two external screws
of the plug part (see also Page
26 Item 10).
If you would like to use the emergency switch-off function,
continue with Section 8.4 on Page 41.
The integrated Emergency Power Off mechanism is
used solely to switch
off the UPS power. This is
done electronically and does not
correspond to an
EMERGENCY-STOP device as per DIN EN ISO 13850
.
7 Operation and Control
7.1 Initial commissioning
Plug the safety plug of the mains connection cable into the
intended, properly fuse-protected safety socket. The UPS is
automatically supplied with power from the public mains. The
UPS starts up in the initialisation phase. All pictograms and LEDs
of the liquid crystal display light up briefly.
If an error indication is received, analyse the display
usi
ng the overview in Chapter 9
, starting on Page
43. If the battery system is not recognised, for
example, go back to Chapter
6, starting on Page 28.
The ex-works presetting of the rated output voltage is 230 V. The
changing of this parameter is described in Section 7.4 on Page 38.
7.1.1 Switching ON the UPS
If the UPS is in the so-called standby mode (e.g. after the
procedures described above), press and hold the "ON/MUTE"
button (for about 3 seconds) until the "ON" message flashes at
the top right of the display. The UPS carries out a brief self-test
and begins normal operation after a few seconds. The display
switches to the UPS status
display. The "OK" message appears
at the top right.
Now switch on your electrical loads one after another. The device
load of the UPS should not exceed the specified rated load of the
i