Operating instructions

14
EN
Efficiency B. 750 PRO > 97% / > 90% / > 83%
with a 50-100% load B.
1000 PRO > 97% / > 90% / > 83%
(ECO / AVR / battery mode) B.
1400 PRO > 97% / > 90% / > 85%
B.
1800 PRO > 97% / > 90% / > 85%
B.
2300 PRO > 97% / > 90% / > 87%
B.
3000 PRO > 97% / > 90% / > 87%
Inherent noise (at 1m distance)
Protect B.750
- B.3000 40 dB(A) in mains mode (ECO)
and load < 70%
Protect B.750
- B.1800 45 dB(A) in mains mode and
Protect B.2300
- B.3000 55 dB(A) load > 70%
Protect B.750
- B.1000 45 dB(A)
Protect B.1400
- B.3000 55 dB(A)
Cooling type External cooling via variable-
speed fan
Operating temperature range 0
°C to +40 °C
Recommended: +15
°C to +25 °C
(depends on battery system)
Storage temperature range -20
°C to +50 °C
Humidity
90% (without condensation)
Set-up altitude Up to 1,000
m at rated power
Up to 2,000
m with 10% power
Up to 3,000
m with 20% reduct.
Max.
transport altitude: 10,000 m
Connections
Mains connection IEC320 C14 (B.750-B.1800)
IEC320 C20 (B.2300-B.3000)
Electrical load connections
Protect B.750
- B.1800 4 x IEC320 C13 (UPS-direct)
4 x IEC320 C13 (manageable)
Protect B.2300
- B.3000 3 x IEC320 C13 (UPS-direct)
1 x IEC320 C19 (UPS-direct)
3 x IEC320 C13 (manageable)
Display Liquid crystal display
Additional 3 LEDs for operating display
Housing colour Blackline, silver front
in battery mode