Operating instructions

12
EN
Rated output current (at 230 Vac)
Protect B.
750 PRO 3.2 A
Protect B.
1000 PRO 4.3 A
Protect B.
1400 PRO 6.1 A
Protect B.
1800 PRO 7.8 A
Protect B.
2300 PRO 10.0 A
Protect B.
3000 PRO 13.0 A
Power factor range 0.8
lag. to 0.9 cap.
with full power output
10% power reduction in the
range
of 0.5 lag. to 0.8 lag.
Transfer time in case of mains failure 2-
6 ms (typical), 8 ms max.
Voltage waveform Sinusoidal, distortion
<
5% THD (linear load)
<
10% THD (non-linear load)
Connection sockets acc. to IEC 320
Overload capacity in mains mode
120% for 5 min
>
120% 150% for 10 s
>
150% for 1 s
in battery mode
110% for 1 min
>
110% 150% for 10 s
>
150% 200% for 500 ms
>
200% for 150 ms
Battery
Coupled
battery
modules
Autonomy times (rated load, cos
ϕ = 0.9 lag.)
with 100% charged battery and at 25 °C
750 VA 1000 VA 1400 VA 1800 VA 2300 VA 3000 VA
with integrated
battery system
3.5
min. 3.5 min. 5 min. 4.5 min.
3.5 min.
4 min.
with 1 ancillary
battery unit
- - - 14 min. - - - 17.5 min. - - -
15 min.
Temperature-dependent
charging voltage Yes
Deep discharge protection
/
Protection against overcharging Yes