2.3 Technical data
Type rating
Protect B. 750 PRO 750 VA (cos ϕ = 0.9 lag.)
675 W
Protect B.
1000 PRO 1000 VA (cos ϕ = 0.9 lag.)
900 W
Protect B.
1400 PRO 1400 VA (cos ϕ = 0.9 lag.)
1260 W
Protect B.
1800 PRO 1800 VA (cos ϕ = 0.9 lag.)
1620 W
Protect B.
2300 PRO 2300 VA (cos ϕ = 0.9 lag.)
2070 W
Protect B.
3000 PRO 3000 VA (cos ϕ = 0.9 lag.)
2700 W
UPS input 1ph~/N/PE
Rated supply voltage 220 / 230 / 240 Vac
Voltage range without battery ±20%
Frequency (automatic detection) 50
/60 Hz ± 5 Hz
Current consumption at 230 Vac, full load and battery charge (max.)
Protect B.
750 PRO 4.0 A
Protect B.
1000 PRO 5.4 A
Protect B.
1400 PRO 7.5 A
Protect B.
1800 PRO 9.7 A
Protect B.
2300 PRO 12.4 A
Protect B.
3000 PRO 16.1 A
Connection Plug acc. to IEC 320
UPS output
Rated output voltage 220 / 230 / 240 Vac ± 10%
(in ECO & AVR
range)
Rated output voltage
tolerance in battery mode ±3%
Frequency in battery mode 50/60
Hz ± 1 Hz
208 Vac with 20%
power reduction